Mitsubishi Electronics GOT1000 Portable Multimedia Player User Manual


 
22. FA TRANSPARENT FUNCTION
22.6 Personal Computer Side Setting
22 - 55
17
ROBOT
CONTROLLER
CONNECTION
18
CNC CONNECTION
19
GOT MULTI-DROP
CONNECTION
20
MULTIPLE-GT14, GT12,
GT11, GT10
CONNECTION FUNCTION
21
MULTI-CHANNEL
FUNCTION
22
FA TRANSPARENT
FUNCTION
22.6.6 Accessing by the MT Works2
This section explains the procedure to set the FA
transparent function of MT Works2 with an example of
connecting to motion controller CPU (Q series).
When connecting the GOT and personal
computer with serial or USB
(1) Connecting the GOT and PLC in bus connection or
direct CPU connection
1. Click [Transfer setup] [Online].
2. The [Transfer setup] is displayed.
3. Set the [Transfer setup]:
PC side I/F : Serial USB
CPU side I/F : GOT
Other Station Setting : No specification
4. Double-click [Serial] of the PLC side I/F to display [PC
side I/F Serial setting].
5. Check-mark either of the following in [PC side I/F
Serial setting].
Mark the [RS-232C] checkbox.
Mark the [USB] checkbox.
When connecting the GOT and PC with serial
When connecting the GOT and PC with USB
6. Double-click [GOT] of the CPU side I/F to display
[CPU side I/F Detailed Setting of GOT].
7. Check-mark either of the following in [CPU side I/F
Detailed Setting of GOT].
Mark the [via GOT(Bus) transparent mode] checkbox.
Mark the [via GOT (direct coupled) transparent mode]
checkbox.
8. The screen returns to [Transfer setup]. Click
[Connection Test] to check if MT Works2 has been
connected to the motion controller (Q mode).
Bus connection
Direct CPU connection