13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13 - 31
9
MELSECNET/H
CONNECTION (PLC
TO PLC NETWORK)
10
MELSECNET/10
CONNECTION (PLC
TO PLC NETWORK)
11
CC-Link IE CONTROLLER
NETWORK
CONNECTION
12
CC-Link IE FIELD
NETWORK
CONNECTION
13
CC-Link CONNECTION
(INTELLIGENT DEVICE
STATION)
14
CC-Link
CONNECTION
(Via G4)
15
INVERTER
CONNECTION
16
SERVO AMPLIFIER
CONNECTION
[Controller Setting] of GT Designer3
(1) When MODEL GT15-J61BT13 CC-Link
communication unit is used
(2) When MODEL GT15-75J61BT13-Z CC-Link
communication unit is used
POINTPOINTPOINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
13.3.1 Setting communication interface
(Communication settings)
Setting of the CC-Link communication unit
(Only when MODEL GT15-75J61BT13-Z
CC-Link communication unit is used)
POINTPOINTPOINT
Setting of the CC-Link communication unit
For the setting method of the CC-Link communication
unit, refer to the following.
13.3.3 Switch setting (Only when MODEL
GT15-75J61BT13-Z CC-Link communication
unit is used)
13.4.7 Connecting to CC-Link module
(A Series)
This section describes the settings of the GOT and CC-
Link module (A Series) in the following case of system
configuration.
POINTPOINTPOINT
CC-Link module (A Series)
For details of the CC-Link module (A Series), refer to
the following manual.
Control & Communication Link System Master/
Local Module Type AJ61BT11/A1SJ61BT11
User's Manual
System configuration
*1 The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0"
Item Set value
Station No. 1: Station No.1
Transmission Rate 0: Online 156kbps
Mode Ver.1: Remote net (Ver.1 mode)
Expanded Cyclic Single (Use default value)
Number of stations occupied
1 Station
Input for Error Station 0: Clear
Retry 3times (Use default value)
Timeout Time 3sec (Use default value)
Delay Time 0ms (Use default value)
Item Set value (Use default value)
Retry 3times
Timeout Time 3sec
Item Set value
Mode setting switch 0: Online (fixed)
Station number setting switch 1: Station No.1
Transmission baudrate setting switch 0: 156kbps
Condition
setting
switches
SW1
(Input data status of the data
link error station)
OFF: Cleared
SW2 (Number of occupied
stations)
OFF: 1 station
*1
<CC-Link module>
(Use the default value for settings other than the following.)
<GOT>
(Use the default value for settings other
than the following.)
Station type : Master station
All connect count
: 1
Mode setting
: Remote net mode
Station No.
: Station No.0
Module mode
: Intelligent mode
Transmission speed
: 156kbps
Station type
: Intelligent device
station
Station No.
: Station No.1
Number of station occupied : Exclusive station 1
Transmission
speed
: 156kbps
[Controller Setting] of GT Designer3
Setting of the CC-Link communication unit
Settings of CC-Link module (A Series)
Sequence program