Mitsubishi Electronics GOT1000 Portable Multimedia Player User Manual


 
11 - 12
11. CC-Link IE CONTROLLER NETWORK CONNECTION
11.4 PLC Side Setting
(c) Routing parameter setting
Up to 64 [Transfer Network No.]s can be set.
However, the same transfer network number
cannot be set twice or more (multiple times).
Therefore, the one that can access to other station
from the request source host GOT is 64 kinds of
[Transfer Network No.]s.
POINTPOINTPOINT
Routing parameter setting of request source
Routing parameter setting is also necessary for the
request source GOT.
For the setting, refer to the following.
11.3.3 Routing parameter setting
Parameter setting (when connecting to C
Controller module)
Use SW3PVC-CCPU-E Ver.3.05F or later for the CC IE
Control utility.
(1) Connection settings between personal computer
and C controller module
: Necessary : As necessary : Not necessary
*1 If the IP address of the C Controller module has been
changed, input the changed IP address or host name.
*2 If the account of the C Controller module has been changed,
input the changed user name and password.
Item Range
Target network No. 1 to 239
Relay network No. 1 to 239
Relay station No. 1 to 120
Item Set value
Setting
necessity at
GOT
connection
Target module
*1
192.168.3.3 (Default)
Write authority Mark the checkbox
User name
*2
target
Password
*2
password
Detailed settings -