13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.3 GOT Side Settings
13 - 11
9
MELSECNET/H
CONNECTION (PLC
TO PLC NETWORK)
10
MELSECNET/10
CONNECTION (PLC
TO PLC NETWORK)
11
CC-Link IE CONTROLLER
NETWORK
CONNECTION
12
CC-Link IE FIELD
NETWORK
CONNECTION
13
CC-Link CONNECTION
(INTELLIGENT DEVICE
STATION)
14
CC-Link
CONNECTION
(Via G4)
15
INVERTER
CONNECTION
16
SERVO AMPLIFIER
CONNECTION
13.3.3 Switch setting (Only when
MODEL GT15-75J61BT13-Z
CC-Link communication unit is
used)
POINTPOINTPOINT
Switch setting of the communication unit
When using the MODEL GT15-J61BT13 CC-Link
communication unit, the switch setting is not needed.
For details of each setting switch and LED, refer to the
following manual.
GT15 CC-Link communication unit User's
Manual
(1) Mode setting switch
(2) Station number setting switch
(3) Transmission baudrate setting switch
(4) Condition setting switches
POINTPOINTPOINT
(1) Switch setting example
For the switch setting example, refer to the
following.
13.4 PLC Side Setting
(2) When the switch setting is changed
When changing the switch setting after mounting
the MODEL GT15-75J61BT13-Z CC-Link
communication unit on the GOT, reset the GOT.
Mode setting
switch
Description Set value
Select the online mode.
(Default: 0)
0 (fixed)
Station
number
setting
switch
Description Set value
Specify the station No. of the CC-
Link communication unit.
(Default: 01)
1 to 64
21
ON
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
(1)
MODE
STATION NO.
BAUDRATE
SW
1
2
ON
HOLD
4
OFF
CLEAR
1
DA
1357
2468
DG NC NC
DB SLD (FG1) NC
10
1
L ERR.
RD
SD
L RUN
RUN
(4)
(3)
(2)
Left side Front side
GT15-75J61BT13-Z
Transmission
baudrate
setting switch
Description Set value
Specify the transmission speed.
(Default: 0)
0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
Condition
setting
switches
Setting
switch
Description Set value
SW1
Specify input data status of
the data link error station.
(Default: OFF)
OFF: Cleared
ON: Held
SW2
Specify the number of stations
occupied.
(Default: OFF)
OFF: 1 station
ON: 4 stations