22 - 40
22. FA TRANSPARENT FUNCTION
22.6 Personal Computer Side Setting
Connecting the GOT and PLC in computer link
connection(when connected to the QJ71C24(N))
(GX Configurator is not supported.)
1. Click [Online] [Transfer Setup] in GX Developer.
2. The [Transfer Setup] is displayed.
3. Set the [Transfer Setup]:
PC side I/F : Serial
PLC side I/F : C24
Other station : No specification
4. Return to [Transfer Setup] and double-click [C24] of
the PLC side I/F to display [PLC side I/F detailed
setting of C24].
5. Check [via GOT transparent mode] for [PLC side I/F
detailed setting of C24].
6. Double-click [Serial] of the PC side I/F to display [PC
side I/F Serial setting].
7. Check-mark either of the following in [PC side I/F
Serial setting].
Mark the [RS-232C] checkbox.
Mark the [USB] checkbox.
8. The screen returns to [Transfer Setup]. Click
[Connection Test] to check if GX Developer has been
connected to the QCPU (Q mode).
When connecting the GOT to PC via modem
When connecting the GOT and PC with serial
When connecting the GOT and PC with USB