5. BUS CONNECTION
5.2 System Configuration
5 - 9
1
PREPARATORY
PROCEDURES FOR
MONITORING
2
DEVICE RANGE
THAT CAN BE SET
3
ACCESS RANGE
FOR MONITORING
4
HOW TO MONITOR
REDUNTANT
SYSTEM
5
BUS CONNECTION
6
DIRECT
CONNECTION TO
CPU
7
COMPUTER LINK
CONNECTION
8
ETHERNET
CONNECTION
5.2.2 Connecting to QnACPU or AnCPU
When one GOT is connected
*1 For the extension cables, refer to MELSEC-A/QnA catalog (L(NA)08024).
*2 When installing the GOT 6.6m or more away from the main base unit, the bus connector conversion box is required.
*3 When using GT15-C EXSS-1, follow the precautions below.
5.4.1 GT15-C [ ] EXSS-1, GT15-C [ ] BS
*4 When using the following functions, use GT15-ABUS(2). GT15-75ABUS(2)L cannot be used.
Used for remote personal computer operation (serial), video display function, multimedia function, operation panel function,
external I/O function, RGB display function, report function (when using a PictBridge compatible printer), hard copy function
(when using a PictBridge compatible printer), sound output function, functions with the CF card unit or CF card extension unit,
Ethernet download, gateway function or MES interface function
However, Ethernet download, gateway function and MES interface function can be used for GT16 by using the Ethernet interface.
Extension base
unit
Bus extension
connector box
GOT
Main base unit
Extension cable
Connection cable 1)
Connection cable 2)
Communication driver
Bus(A/QnA)
PLC
Connection cable 2)
GOT
Max. distance
Main
base
Extension
cable
*1
Extens
ion
base
Connection cable 1)
Bus
connector
conversion
box
*2
Option device
Model
Main
base
-- - -
GT15-C12NB(1.2m)
GT15-C30NB(3m)
GT15-C50NB(5m)
GT15-75ABUSL
GT15-75ABUS2L
GT15-ABUS
GT15-ABUS2
Between main base and
GOT: 6.6m
- (Built into GOT)
--
GT15-AC06B(0.6m)
GT15-AC12B(1.2m)
GT15-AC30B(3m)
GT15-AC50B(5m)
A7GT
-CNB
GT15-C100EXSS-1(10m)
GT15-C200EXSS-1(20m)
GT15-C300EXSS-1(30m)
*3
GT15-75ABUSL
GT15-75ABUS2L
GT15-ABUS
GT15-ABUS2
Between main base and
GOT: 36.6m
(Including between main
base and bus connector
conversion box)
Between main base and
bus connector conversion
box: 6.6m
- (Built into GOT)
Main
base
Extension
cable
Extens
ion
base
--
GT15-C12NB(1.2m)
GT15-C30NB(3m)
GT15-C50NB(5m)
GT15-75ABUSL
GT15-75ABUS2L
GT15-ABUS
GT15-ABUS2
Between main base and
GOT: 6.6m
(Including the extension
cable length)
- (Built into GOT)
GT15-AC06B(0.6m)
GT15-AC12B(1.2m)
GT15-AC30B(3m)
GT15-AC50B(5m)
A7GT
-CNB
GT15-C100EXSS-1(10m)
GT15-C200EXSS-1(20m)
GT15-C300EXSS-1(30m)
GT15-75ABUSL
GT15-75ABUS2L
GT15-ABUS
GT15-ABUS2
Between main base and
GOT: 36.6m
Between main base and
bus connector conversion
box: 6.6m
(Including the extension
cable length)
- (Built into GOT)