19. GOT MULTI-DROP CONNECTION
19.6 Setting of Serial Multi-Drop Connection Unit
19 - 27
17
ROBOT
CONTROLLER
CONNECTION
18
CNC CONNECTION
19
GOT MULTI-DROP
CONNECTION
20
MULTIPLE-GT14, GT12,
GT11, GT10
CONNECTION FUNCTION
21
MULTI-CHANNEL
FUNCTION
22
FA TRANSPARENT
FUNCTION
Exporting/Importing the communication
setting contents
(1) Export
1. After determining the storage location as necessary,
name the file and save it.
The file format is [*.ini] (fixed).
(2) Import
1. Enter the name of the file previously saved and open
the file.
The file format is [*.ini] (fixed).
Communication detail settings
Make the settings according to the usage environment.
(3) For the connection with GOT
(4) For the connected equipment
Set the communication detail settings of the driver for
controllers according to the connection type.
Refer to each chapter.
Item Description Range
Transmission Speed
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 115200bps)
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Retry
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times
out.
(Default: 0time)
0 to 5times
Timeout Time
Set the time period for a
communication to time out.
(Default: 3sec)
3 to 30sec
Delay Time
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 0ms)
0 to 300 ms