[Controller Setting] and [Ethernet] of GT
Designer3
(1) Controller setting
(2) Ethernet setting
*1 Set the value according to the IP address of the connected
PLC.
*2 Set the value according to the Port No. of the connected
PLC.
For details, refer to the following.
8.3.3 Ethernet setting
POINTPOINTPOINT
[Controller Setting] and [Ethernet] of GT Designer3
For [Controller Setting] and [Ethernet] of GT
Designer3, refer to the following.
8.3.1 Setting communication interface
(Communication settings)
Confirming the communication state of
Ethernet module
(1) When using the Command Prompt of Windows
.
Execute a Ping command at the Command Prompt of
Windows
.
(a) When normal communication
C:\>Ping 192.168.0.19
Reply from 192.168.0.19: bytes=32 time<1ms
TTL=64
(b) When abnormal communication
C:\>Ping 192.168.0.19
Request timed out.
(2) When abnormal communication
At abnormal communication, check the followings and
execute the Ping command again.
• Mounting condition of Ethernet communication unit
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• IP address of GOT specified by Ping command
POINTPOINTPOINT
Ethernet diagnostics of FX Configurator-EN
Ethernet diagnostics of FX Configurator-EN is
available to a Ping test from the PLC.
For details of Ethernet diagnostics of FX Configurator-
EN, refer to the following manual.
FX Configurator-EN Operation manual
Item Setting (Use default value.)
GOT NET No. 1
GOT PLC No. 1
GOT IP Address 192.168.0.18
GOT Port No.
(Communication)
5019
GOT Port No.
(Ethernet Download)
5014
Default Gateway 0.0.0.0
Subnet Mask 255.255.255.0
Retry 3times
Startup Time 3sec
Timeout Time 3sec
Delay Time 0ms
Item Setting
Ethernet
setting No.1
Host *
N/W No. 1
PLC No. 2
Type FX (fixed)
IP address
192.168.0.19
*1
Port No.
5551
*2
Communication TCP (fixed)