11 - 14
11. CC-Link IE CONTROLLER NETWORK CONNECTION
11.4 PLC Side Setting
(c) Routing parameter setting
Up to 64 [Transfer Network No.]s can be set.
However, the same transfer network number
cannot be set twice or more (multiple times).
Therefore, the one that can access to other station
from the request source host GOT is 64 kinds of
[Transfer Network No.]s.
POINTPOINTPOINT
Routing parameter setting of request source
Routing parameter setting is also necessary for the
request source GOT.
For the setting, refer to the following.
11.3.3 Routing parameter setting
GT Designer3 [Communication settings] of
System configuration1 (Network Type: CC IE
Control)
POINTPOINTPOINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
11.3.1 Setting communication interface
(Communication settings)
Item Range
Transfer target network No. 1 to 239
Relay network No. 1 to 239
Relay station No. 1 to 120
Item Set value
Network Type CC IE Control
Network No. 1: Network No.1
Station No. 2: Station No.2
Mode Setting Online (auto. reconnection)
Retry 3times (Use default value)
Timeout Time 3sec (Use default value)
Delay Time 0ms (Use default value)
Refresh Interval 1ms (Use default value)
Monitor Speed High (Use default value)