2 - 14
2. DEVICE RANGE THAT CAN BE SET
2.7 MELSEC-WS
2.7 MELSEC-WS
The device ranges that can be set when selecting
[MELSEC-WS] as the controller type are as follows.
POINTPOINTPOINT
(1) Devices of MELSEC-WS
Only reading is possible for all devices.
(2) Device settings of MELSEC-WS
Input(I), Output(Q)
Logic result(LQ), Logic input(LI)
EFI input(EI)
EFI output(EQ)
(3) Engineering software for MELSEC-WS and device
representation of GT Designer3
The engineering software for MELSEC-WS and
the device representation of GT Designer3 are
different. Set the device by referring to the
following table.
*1 When the mapping position is changed by the MELSEC-WS
engineering software, a mismatch occurs between virtual
devices on GOT and MELSEC-WS mapping devices.
When mapping is changed, use D devices or LD devices.
Device Setting range
Device No.
representation
Bit device
Input (I) I1.1 to I12.8
Decimal
+Decimal
Output (Q) Q1.1 to Q12.8
Logic result (LQ) LQ0.0 to LQ3.7
Logic input (LI) LI0.0 to LI3.7
Word device bit
Specified bit of the
following word devices
-
Word device
Data (byte)(D) D0 to D99
Decimal
Data (word)(W) W0 to W49
EFI input (byte)(EI) EI110 to EI233
Decimal
+Decimal
+Decimal
EFI output (byte)(EQ) EQ10 to EQ22
Decimal
+Decimal
Logic input (byte)(LD) LD0 to LD3 Decimal
Logic input (word)
(LW) LW0 to LW1 Decimal
Device
name
Input position(1 to 8)
Module number(1 to 12)
Device
name
Bit position(0 to 7)
Byte number(0 to 3)
Device
name
Device number(1 to 3)
Byte number(0 to 3)
EFI number(1 to 2)
Device
name
EFI number(1 to 3)
Byte number(0 to 2)
Device
GT Designer3
Engineering software for
MELSEC-WS
I
*1
I.
(1-12(Dec)): Module number
(1-8): Input position
[].I
: I/O model name
(such as XTIO)
(1-12(Dec)): Module number
(1-8): Input position
Q
*1
Q.
(1-12(Dec)): Module number
(1-8): Output position
[].Q
: I/O model name
(such as XTIO)
(1-12(Dec)): Module number
(1-8): Output position
LQ
*1
LQ .
(0-3): Byte number
(0-7): Bit position
.
: "Result"
(0-3): Byte number
(0-7): Bit position
LI
*1
LI .
(0-3): Byte number
(0-7): Bit position
[0] . .
: CPU type (CPU0, CPU1)
(0-3): Byte number
(0-7): Bit position
EI
*1
EI
(1-2): EFI number
(1-3): Device number
(0-3): Byte number
[0].EFI : , Byte
: CPU type (CPU0, CPU1)
(1-2): EFI number
(1-3): Device number
(0-3): Byte number
EQ
*1
EQ
(1-2): EFI number
(0-2): Byte number
[0].EFI :1, Byte
: CPU type (CPU0, CPU1)
(1-2): EFI number
(0-2): Byte number
D
D
(0-99(Dec)): Byte number
RS232 data
(Safety controller to RS232)
W
W
(0-49(Dec)): Word number
Word virtualization of D
device
W0= (D1(Upper bits),
D0(Lower bits))
GOT independent device
(Not available)
LD
LD
(0-3): Byte number
RS232 data
(Safety controller to RS232)
LW
LW
(0-1): Word number
Word virtualization of LD
device
LW0= (LD1(Upper bits),
LD0(Lower bits))
GOT independent device