Mitsubishi Electronics GOT1000 Portable Multimedia Player User Manual


 
22 - 46
22. FA TRANSPARENT FUNCTION
22.6 Personal Computer Side Setting
(b) Connecting to FXCPU
10.Specify the number for [Network No.] and [Station
No.] same as the number assigned to the Ethernet
module.
When [QnUDE(H)] is set for [PLC type], the setting is
not required.
11. Specify the IP address for [IP Address] same as the
IP address assigned to the built-in Ethernet port
QCPU or Ethernet module.
12.The screen returns to [Transfer Setup Connection1].
Click [Connection Test] to check if GX Works2 has
been connected to the QCPU (Q mode).
1. Click the Connection Destination view
[Connection Destination] [(Connection target data
name)] in the Navigation window of GX Works2.
2. The [Transfer Setup Connection1] is displayed.
3. Set the [Transfer Setup Connection1]:
PC side I/F : Serial USB
PLC side I/F : GOT
Other Station Setting : No Specification
4. Double-click [Serial USB] of the PC side I/F to display
[PC side I/F Serial Setting].
5. Check-mark either of the following in [PC side I/F
Serial Setting].
Mark the [RS-232C] checkbox.
Mark the [USB] checkbox.
6. Double-click [GOT] of the PLC side I/F to display
[PLC side I/F Detailed Setting of GOT].
7. On the [PLC side I/F Detailed Setting of GOT], mark
the [via GOT(Ethernet) transparent mode] checkbox
and click [Setting...].
When connecting the GOT and PC with serial
When connecting the GOT and PC with USB
PLC side I/F Detailed Setting of GOT
PLC Module/CC IE Field Ethernet Adapter
Setup
Setup
PLC Mode
via GOT(direct coupled) transparent mode
via GOT(Ethernet) transparent mode
Computer Type
Station No.
Parity
Sum Check
Data Bit 8
Stop Bit 1
FX3U-ENET-ADP-0.0.0.0.
Setting...
OK
Cancel
FXCPU
C24
QJ71C24
0
Odd
Exists