Mitsubishi Electronics GOT1000 Portable Multimedia Player User Manual


 
8 - 42
8. ETHERNET CONNECTION
8.4 PLC Side Setting
8.4.8 Connecting to Display I/F
(CNC C70)
This section describes the settings of the GOT and Display
I/F (CNC C70) in the following case of the system
configuration.
POINTPOINTPOINT
Display I/F (CNC C70)
For details of the Display I/F (CNC C70), refer to the
following manual.
C70 Series SET UP MANUAL
System configuration
IP address settings of CNC C70
(1) Remote monitor tool
: Necessary : As necessary : Not necessary
(2) CNC monitor
: Necessary : As necessary : Not necessary
(3) Communication check
The CNC C70 can communicate with the GOT when
INIT.LED of the CNC C70 is lit.
For confirming the communication state, refer to the
following.
Checking communication state of CNC C70
[Controller Setting] and [Ethernet] of GT
Designer3
(1) Controller setting
Item Set value
Setting necessity at
GOT connection
IP address 192.168.0.19
Subnet mask 255.255.255.0
Gateway address 0.0.0.0
Port number 64758 (fixed)
Speed auto/10M 0 (fixed)
<GOT> (The settings other than the
following are set to the default)
Network No. : 1
PLC No. : 1
IP address : 192.168.0.18
Port No. : 5001
Communication format: UDP (fixed)
Network No. : 239
PLC No. : 2
IP address : 192.168.0.19
Port No. : 5001
Communication format
: UDP(fixed)
<Q17nNCCPU> (The settings other than the
following are set to the default)
[Controller Setting] and [Ethernet] of GT
Designer3
IP address settings of CNC C70
Item Set value
Setting necessity at
GOT connection
IP address 192.168.0.19
Subnet mask 255.255.255.0
Gateway address
0.0.0.0
Port number 64758 (fixed)
Speed auto/10M
0 (fixed)
Item Set value (Use default value)
GOT NET No. 1
GOT PLC No. 1
GOT IP Address 192.168.0.18
GOT Port No.
(Communication)
5001
GOT Port No.
(Ethernet Download)
5012
Default Gateway 0.0.0.0
Subnet Mask 255.255.255.0
Retry 3times
Startup Time 3sec
Timeout Time 3sec
Delay Time 0ms