13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13.4 PLC Side Setting
The GOT operates as the stations of which are shown
below in the CC-Link system.
The switch settings and parameter settings of the PLC side
(CC-Link module) are described in 13.4.1 to 13.4.7.
HINTHINTHINT
Number of stations occupied
The number of stations occupied is setting for
determining number of link device points (RX/RY/
RWw/RWr) used by the GOT.
To use multiple numbers of link device points in the
case of cyclic transmission between the GOT and CC-
Link module, set the number of stations occupied as
the exclusive station 4.
The number of link device points at the exclusive
station 1 and 4 is shown below.
CC-Link Ver.2
CC-Link Ver.1
Station data Description
Station type
Intelligent device station, Ver.1 intelligent device
station or Ver.2 intelligent device station
Number of stations
occupied
Station 1 or Station 4
Model name Refer to
CC-Link
module
(Q Series)
Connecting
with
Ver.1
compatible
QJ61BT11,
QJ61BT11N
13.4.1
Connecting
with Ver.2
compatible
QJ61BT11N 13.4.2
Connecting
with Ver.1/
Ver.2
compatibles
mixed
QJ61BT11N 13.4.3
CC-Link module
(QnA Series)
AJ61QBT11,
A1SJ61QBT11
13.4.6
CC-Link module
(A Series)
AJ61BT11,
A1SJ61BT11
13.4.7
Link
device
Expanded cyclic setting
Single Double Quadruple Octuple
Exclu
sive
statio
n 1
Exclu
sive
statio
n 4
Exclu
sive
statio
n 1
Exclu
sive
statio
n 4
Exclu
sive
statio
n 1
Exclu
sive
statio
n 4
Exclu
sive
statio
n 1
Exclu
sive
statio
n 4
Remote
input (RX)
32
points
128
points
32
points
224
points
64
points
448
points
128
points
896
points
Remote
output (RY)
32
points
128
points
32
points
224
points
64
points
448
points
128
points
896
points
Remote
register
(RWw)
4
points
16
points
8
points
32
points
16
points
64
points
32
points
128
points
Remote
register
(RWr)
4
points
16
points
8
points
32
points
16
points
64
points
32
points
128
points
Link device
Number of stations occupied
Exclusive station Exclusive station 4
Remote input (RX) 32 points 128 points
Remote output (RY) 32 points 128 points
Remote register (RWw) 4 points 16 points
Remote register (RWr) 4 points 16 points