11 - 10
11. CC-Link IE CONTROLLER NETWORK CONNECTION
11.4 PLC Side Setting
11.4 PLC Side Setting
This section describes the settings of the GOT and CC-
Link IE controller network module in the following case of
system configuration.
POINTPOINTPOINT
CC-Link IE Controller Network module
For details of the CC-Link IE Controller Network
module, refer to the following manual.
CC-Link IE Controller Network Reference
Manual
System configuration1
(Network Type: CC IE Control)
*1 The CC-Link IE Controller Network module is mounted on
slot 0 of the base unit.
The start I/O No. of the CC-Link IE Controller Network
module is set at [0].
POINTPOINTPOINT
When connecting to Q170MCPU
When connected to Q170MCPU, the start I/O No. of
the CC-Link IE Controller Network module is set to
"70".
System configuration2
(Network Type: CC IE Control extended mode)
*1 The CC-Link IE Controller Network module is mounted on
slot 0 of the base unit.
The start I/O No. of the CC-Link IE Controller Network
module is set at [0].
<CC-Link IE Controller Network module> *
1
(Use the default value for settings other than the following.)
Station No. : 1
Mode : Online
Network type : CC IE Control (Control station)
Network No. : 1
Total stations : 2
Network range assignment :
CC-Link IE Controller Network
<GOT>
(Use the default value for settings other
than the following.)
LB0000H to LB00FFH
LW00000H to LW000FFH
Network type : CC IE Control
Network No. : 1
Station No. : 2
Made Setting : Online (auto,reconnection)
Network range assignment :
Monitor Speed : High
LB0100H to LB01FFH
LW00100H to LW001FFH
■ GT Designer3 [Communication settings] of System
configuration1 (Network Type: CC IE Control)
■ [Network parameter] of GX Developer
<CC-Link IE Controller Network module> *
1
(Use the default value for settings other than the following.)
Station No. : 1
Mode : Online
Network type : CC IE Control extended mode
(Control station)
Network No. : 1
Total stations : 2
Network range assignment :
CC-Link IE Controller Network
<GOT>
(Use the default value for settings other
than the following.)
LB0000H to LB00FFH
LW00000H to LW000FFH
Network type : CC IE Control extended mode
Network No. : 1
Station No. : 2
Made Setting : Online (auto,reconnection)
Network range assignment :
Monitor Speed : High
LB0100H to LB01FFH
LW00100H to LW001FFH