13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
(3) Transmission speed setting switch
: Necessary : As necessary : Not necessary
*1 Specify the same transmission speed as that of the GOT.
(4) Condition setting switches
: Necessary : As necessary : Not necessary
*2 Will be valid when the CC-Link module is the local station.
In the case of the master station, turn off it.
POINTPOINTPOINT
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the
PLC CPU.
Parameter setting
There are two methods for the parameter setting:
perform the setting from [Network parameter] of GX
Developer and the sequence program.
Performing it from the [Network parameter] of the GX
Developer can be set only when the PLC CPU and the
CC-Link module use the function version B or later.
(1) Setting from [Network parameter] of GX Developer
(a) Network parameter
: Necessary : As necessary : Not necessary
Transmission
speed setting
switch
Description Set value
Setting
necessity at
GOT
connection
Transmission speed
setting (156kbps)
*1
0
Condition setting
switches
Setting
switch
Description
Set
value
Setting
necessity at
GOT
connection
SW1
Station type
(Master
station/Local
station)
OFF
(fixed)
SW2
Not used
OFF
(fixed)
SW3
SW4
Input data
status of the
data link error
station (clear)
OFF
SW5 Number of
stations
occupied
*2
OFF
(fixed)
SW6
SW7
Not used
OFF
(fixed)
SW8
B RATE
0156K
1625K
22. 5M
35M
410M
0
1
9
8
7
6
5
4
3
2
12345678
O N
1
2
3
4
5
6
7
8
M / L
CLR
1/2
S. M
HLD
3/4
SW OFF ON
1/4 2/3
Item Set value
Setting
necessity at
GOT
connection
No. of boards in module 1
Start I/O No. 0000
H
Type Master station (fixed)
All connect count 1
Remote input (RX) X400
Remote output (RY) Y400
Remote register (RWr) D300
Remote register (RWw) D200
Special relay (SB) B0
Special register (SW) W0
Retry count
(Use default value)
Automatic reconnection
station count
Wait master station No.
PLC down select
Scan mode setting
Delay information setting
Station information setting Refer to (2)