Mitsubishi Electronics GOT1000 Portable Multimedia Player User Manual


 
7. COMPUTER LINK CONNECTION
7.2 System Configuration
7 - 9
1
PREPARATORY
PROCEDURES FOR
MONITORING
2
DEVICE RANGE
THAT CAN BE SET
3
ACCESS RANGE
FOR MONITORING
4
HOW TO MONITOR
REDUNTANT
SYSTEM
5
BUS CONNECTION
6
DIRECT
CONNECTION TO
CPU
7
COMPUTER LINK
CONNECTION
8
ETHERNET
CONNECTION
7.2.3 Connecting to QCPU (A mode)
*1 For the system configuration on the computer link module side, refer to the following manual.
Computer Link Module (Com. link func./Print. func.) User’s Manual
*2 Connect it to the RS-232 interface (built into GOT). It cannot be mounted on GT1655 and GT155 .
*3 Use the RS-232 connection model.
*4 Use the RS-422 connection model.
Computer
link module
QCPU
(A mode)
GOT
Connection cable
Communication driver
( For GT16, GT15, GT14, GT12, GT11)
A/QnA/L/Q CPU,LJ71C24,QJ71C24
( For GT10)
AJ71C24/UC24
Communication driver
PLC Connection cable GOT
Number of
connectable
equipment
Model name
Computer link
module
*1
Commun
ication
type
Cable model
Max.
distance
Option device Model
MELSEC-Q
(A mode)
A1SJ71UC24-R2
A1SJ71C24-R2
A1SJ71UC24-PRF
A1SJ71C24-PRF
RS-232
GT09-C30R2-9P(3m)
or
RS232 connection
diagram 1)
15m
- (Built into GOT)
1 GOT for 1 computer
link module
GT15-RS2-9P
RS232 connection
diagram 3)
15m - (Built into GOT)
*3
A1SJ71UC24-R4
A1SJ71C24-R4
RS-422
RS422 connection
diagram 2)
500m - (Built into GOT)
GT09-C30R4-6C(3m)
GT09-C100R4-6C(10m)
GT09-C200R4-6C(20m)
GT09-C300R4-6C(30m)
or
RS422 connection
diagram 1)
500m
GT16-C02R4-9S
GT15-RS2T4-9P
*2
GT15-RS4-9S
- (Built into GOT)
RS422 connection
diagram 3)
500m - (Built into GOT)
*4