13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
(b) Station information setting
: Necessary : As necessary : Not necessary
*1 When the [Mode] of the CC-Link module is set at [Remote
net - (Ver. 2 mode)], [Remote station points] can be set.
[Remote station points] is a setting for the remote I/O station.
The default value (32 points) must be used on the GOT.
*2 Set the same setting as that of the GOT.
POINTPOINTPOINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
Parameter setting (when connecting to C
Controller module)
Use SW3PVC-CCPU-E Ver.3.05F or later for the CC-
Link utility.
(1) Connection settings
: Necessary : As necessary : Not necessary
*1 If the IP address of the C Controller module has been
changed, input the changed IP address or host name.
*2 If the account of the C Controller module has been changed,
input the changed user name and password.
Item
*1
Set value
Setting
necessity at
GOT
connection
Station type
Ver.2 intelligent device
station (fixed)
Expanded cyclic setting
*2
Single
Exclusive station count
*2
Exclusive station 1
Remote station points 32 points (fixed)
Reserve/invalid station select No setting
Intelligent buffer select (word)
(Use default value)
Item Set value
Setting
necessity at
GOT connection
Target module
*1
192.168.3.3 (Default)
Write authority Mark the checkbox
User name
*2
target
Password
*2
password
Detailed settings -