Mitsubishi Electronics GOT1000 Portable Multimedia Player User Manual


 
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13 - 19
9
MELSECNET/H
CONNECTION (PLC
TO PLC NETWORK)
10
MELSECNET/10
CONNECTION (PLC
TO PLC NETWORK)
11
CC-Link IE CONTROLLER
NETWORK
CONNECTION
12
CC-Link IE FIELD
NETWORK
CONNECTION
13
CC-Link CONNECTION
(INTELLIGENT DEVICE
STATION)
14
CC-Link
CONNECTION
(Via G4)
15
INVERTER
CONNECTION
16
SERVO AMPLIFIER
CONNECTION
(2) CC-Link Utility's [Parameter Settings]
(a) Parameter settings
: Necessary : As necessary : Not necessary
*1 When the [Mode] of the CC-Link module is set at [Remote
net - (Ver. 2 mode)], [Remote station points] can be set.
[Remote station points] is a setting for the remote I/O station.
The default value (32 points) must be used on the GOT.
*2 Set the same setting as that of the GOT.
POINTPOINTPOINT
When changing the network parameter
After writing the network parameter to the C Controller
module, either turn the C Controller module OFF and
then ON or reset it.
[Communication settings] of GT Designer3
POINTPOINTPOINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
13.3.1 Setting communication interface
(Communication settings)
Item
*1
Set value
Setting
necessity at
GOT
connection
Number of modules 1
Target module 1
Start I/O No. 0000
H
Channel No. (Use default value)
Operation settings
Type Master station
Mode
Remote net
(Ver.2 mode)
Expanded cyclic setting Single
Occupied number Exclusive station 1
Error event: input data
status
Clear
CPU stop: data link status Refresh
Other settings (Use default value)
Station information settings
All connect count 1
Station Type
Sta.
No.1
Ver.2 intelligent device
station
Expanded cyclic
setting
*2
Sta.
No.1
Single
Occupied number
*2
Sta.
No.1
Exclusive station 1
Remote station points
Sta.
No.1
32 points
Reserve/invalid
station select
Sta.
No.1
No setting
Intelligent buffer select
(word)
(Use default value)
Item Set value
Station No. 1: Station No.1
Transmission Rate 0: Online 156kbps
Mode Ver.2: Remote net (Ver.2 mode)
Expanded Cyclic Single
Number of stations occupied 1 Station
Input for Error Station Clear
Retry 3times (Use default value)
Timeout Time 3sec (Use default value)
Delay Time 0ms (Use default value)