13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13 - 25
9
MELSECNET/H
CONNECTION (PLC
TO PLC NETWORK)
10
MELSECNET/10
CONNECTION (PLC
TO PLC NETWORK)
11
CC-Link IE CONTROLLER
NETWORK
CONNECTION
12
CC-Link IE FIELD
NETWORK
CONNECTION
13
CC-Link CONNECTION
(INTELLIGENT DEVICE
STATION)
14
CC-Link
CONNECTION
(Via G4)
15
INVERTER
CONNECTION
16
SERVO AMPLIFIER
CONNECTION
(2) Station information setting
: Necessary : As necessary : Not necessary
*1 When the [Mode] of the CC-Link module is set at [Remote
net - (Ver. 1 mode)], [Remote station points] cannot be set.
*2 Set the same setting as that of the GOT.
POINTPOINTPOINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
[Controller Setting] of GT Designer3
POINTPOINTPOINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
13.3.1 Setting communication interface
(Communication settings)
13.4.5 Connecting to MELSEC-L
series with CC-Link Ver.2
compatible
This section describes the settings of the GOT and
MELSEC-L in the following case of the system
configuration.
POINTPOINTPOINT
(1) CC-Link module (L Series)
For details of the CC-Link module (L Series), refer
to the following manual.
MELSEC-L CC-Link System Master/Local
Module User's Manual
(2) CC-Link function built-in CPU
For details on the CC-Link function built-in CPU,
refer to the following manual.
MELSEC-L CC-Link System Master/Local
Module User's Manual
System configuration
(Example when using CC-Link module (L Series))
Item
*1
Set value
Setting
necessity at
GOT
connection
Station type
Intelligent
device station (fixed)
Exclusive station count
*2
Exclusive station 1
Reserve/invalid station
select
No setting
Intelligent buffer select
(word)
(Use default value)
Item Set value
Station No. 1: Station No.1
Transmission Rate 0: Online 156kbps
Mode Ver.1: Remote net (Ver.1 mode)
Expanded Cyclic Single (Use default value)
Number of stations occupied 1 Station
Input for Error Station 0: Clear
Retry 3times (Use default value)
Timeout Time 3sec (Use default value)
Delay Time 0ms (Use default value)
<CC-Link module>
*1
Type : Master station
Station No. : Station No.0
Mode : Remote net (Ver.3 mode)
All connect count : 1
Transmission speed : 156kbps
<GOT>
(Use the default value for settings other
than the following.)
Station type : Intelligent device
station
Station No. : Station No.1
Expanded cyclic setting : Single
Number of
stations occupied
: Exclusive station
Transmission speed : 156kbps
(Use the default value for the settings other than the following.)
[Controller Setting] of GT Designer3
[Network parameter] of GX Developer