8 - 44
8. ETHERNET CONNECTION
8.4 PLC Side Setting
8.4.9 Connecting to CC-Link IE Field
Network Ethernet Adapter
Module
This section describes the settings of the GOT, Ethernet
adapter module and the PLC in the following system
configuration.
System configuration
*1 Set the GOT network No. according to the third octet
(network No.) of the Ethernet adapter module IP address.
*2 The CC-Link IE Field Network Master/Local module is
mounted on slot 0 of the base unit.
The start I/O No. of the CC-Link IE Field Network Master/
Local module is set at [0].
GX Works2 network parameter
Ethernet/CC IE/MELSECNET
For details of the setting contents of PLC side, refer to the
following manual.
MELSEC-Q CC-Link IE Field Network Master/
Local Module User's Manual
(1) Network Type, Network No., Total Stations setting
Example: Master station setting
(2) Routing parameter setting
Set the followings as necessary.
Up to 64 [Transfer Network No.]s can be set.
However, the same transfer network number cannot be
set twice or more (multiple times).
Therefore, the one that can access to other station from
the request source host GOT is 64 kinds of [Transfer
Network No.]s.
<GOT>
(Use default value for settings other than the following.)
Network No.
:3
PC No. :1
IP address
:192.168.3.18
Port No.
:5001
Communication
format
:UDP (fixed)
Ethernet
CC-Link IE Field Network
HUB
<Ethernet adapter module>
(Use default value for settings other than the following.)
Ethernet setting
IP address
CC-Link IE Field Network setting
Network No.
Station No.
:192.168.3.30
:1
:1
<CC-Link IE Field Network Master/Local module>
(Use default value for settings other than the following.)
Network Type
Network No.
PC No.
Total Stations
: CC IE Field (Master station)
: 1
: 0
: 2
*2
*1
<CC-Link IE Field Network Master/Local module>
(Use default value for settings other than the following.)
Network Type
Network No.
PC No.
: CC IE Field (Local station)
: 1
: 2
*2
Item
Set value
Master station Local station
Network type
CC IE Field
(Master station)
CC IE Field
(Local station)
Network No. 1 1
Total Stations 2 -
Station No. 0 (fixed) 2
Item Range
Transfer Network No. 1 to 239
Relay Network No. 1 to 239
Relay Station No. 1 to 64