Mitsubishi Electronics GOT1000 Portable Multimedia Player User Manual


 
6. DIRECT CONNECTION TO CPU
6.2 System Configuration
6 - 7
1
PREPARATORY
PROCEDURES FOR
MONITORING
2
DEVICE RANGE
THAT CAN BE SET
3
ACCESS RANGE
FOR MONITORING
4
HOW TO MONITOR
REDUNTANT
SYSTEM
5
BUS CONNECTION
6
DIRECT
CONNECTION TO
CPU
7
COMPUTER LINK
CONNECTION
8
ETHERNET
CONNECTION
6.2.2 Connecting to LCPU
*1 Connect it to the RS-232 interface (built into GOT). It cannot be mounted on GT1655 and GT155 .
*2 For the connection to GOT, refer to the connection diagram. ( RS232 connection diagram 3))
*3 For the connection to GOT, refer to the connection diagram. ( RS422 connection diagram 2))
*4 For details of the GOT multi-drop connection, refer to the following.
19. GOT MULTI-DROP CONNECTION
*5 GT14, GT12, GT11 and GT10 are available for the multiple-GT14, GT12, GT11, GT10 connection function to connect up to two
GOTs.
20. MULTIPLE-GT14, GT12, GT11, GT10 CONNECTION FUNCTION
*6 Use the RS-232 connection model.
*7 Use the RS-422 connection model.
RS-422 connector
conversion cable
LCPU Adapter GOT
Connection cable
Communication driver
QnA/L/Q CPU
( For GT10)
Communication driver
( For GT16, GT15, GT14, GT12, GT11)
A/QnA/L/Q CPU,LJ71C24,QJ71C24
PLC Connection cable GOT
Number of
connectable
equipment
*5
Model
name
Adapter
RS-422 connector
conversion cable
Communi
cation
type
Cable model
Max.
distance
Option device Model
MELSEC-L
L6ADP-R2 - RS-232
GT01-C30R2-6P(3m) 3m
- (Built into GOT)
1 GOT for 1 PLC
GT15-RS2-9P
GT01-RS4-M
*4
-
GT10-C30R2-6P(3m)
*2
3m - (Built into GOT)
*6
L6ADP-R2
FA-CNV2402CBL(0.2m)
FA-CNV2405CBL(0.5m)
RS-422
GT01-C30R4-25P(3m)
GT01-C100R4-25P(10m)
GT01-C200R4-25P(20m)
GT01-C300R4-25P(30m)
30m
GT16-C02R4-9S
GT15-RS2T4-9P
*1
GT15-RS4-9S
- (Built into GOT)
GT01-RS4-M
*4
-
GT10-C30R4-25P(3m)
GT10-C100R4-25P(10m)
GT10-C200R4-25P(20m)
GT10-C300R4-25P(30m)
*3
30m - (Built into GOT)
*7