Mitsubishi Electronics GOT1000 Portable Multimedia Player User Manual


 
8 - 12
8. ETHERNET CONNECTION
8.2 System Configuration
8.2.3 Connecting to Display I/F
*1 The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standard.
*2 When connecting GT16 of the function version A to an equipment that meets the 10BASE (-T/2/5) standard, use the switching
hub and operate in a 10Mbps/100Mbps mixed environment.
For how to check the function version, refer to the following.
GT16 User's Manual (Hardware)
*3 A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
10BASE-T: Max. 4 nodes for a cascade connection (500m)
100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*4 For the system configuration of the CNC C70, refer to the following manual.
C70 Series SET UP MANUAL
*5 Select [Q17nNC] for [Controller Type] in [Ethernet] of GT Designer3.
For [Ethernet] of GT Designer3, refer to the following.
8.3.3 Ethernet setting
*6 GT14 models compatible with Ethernet connection are only GT1455-QTBDE and GT1450-QLBDE.
Ethernet(MELSEC),Q17nNC,CRnD-700
Communication driver
CNC
C70
GOT
Connection cable
PLC CPU
PLC
Connection cable
*1
Maximum
segment
length
*3
GOT
Number of connectable
equipment
Model name
Communication
type
Option device Model
CNC C70
(Q173NCCPU)
*4*5
Ethernet
Twisted pair cable
10BASE-T
Shielded twisted pair cable (STP) or
unshielded twisted pair cable (UTP):
Category 3, 4, and 5
100BASE-TX
Shielded twisted pair cable (STP):
Category 5 and 5e
100m
- (Built into GOT)
*2
*6
16 GOTs for 1 network
GT15-J71E71-100