9-1527STO-DATA (Stored Data)
9
The A/B Carrier Boot Image Test (#837) runs only at system boot time.
A Carrier and B Carrier Tape Checksum Tests
(#829/#830)
A checksum is done on the primary copy of the boot image on the tape and also
on the secondary copy of the boot image on the tape. A comparison is made to
verify that these two checksums are the same. This test is run as part of the
test
stored-data long
demand test.
B Carrier Tape to Disk Consistency Test
(#834)
XXX
A to B Carrier Tape Consistency Test
(#835)
XX XX
A to B Carrier Disk Consistency Test
(#836)
XX
Table 9-579. TESTS #829 and #830 Tape Checksum Tests
Error
Code
Tes t
Result Description/ Recommendation
1303 ABORT Could not run the testinternal MSS error
1. Retry the command
1304 ABORT Could not allocate the Mass Storage System to run this test
1. Retry the command at 1-minute intervals for a maximum of 5 retries.
2. If the test continues to abort, verify that the daily translation-save operation
is not in progress (Use the display system-parameters maintenance
command to display the start time for scheduled maintenance and the
"y/n" option for saving translation daily).
1338 ABORT Could not run the test on the Standby SPEInterchange pending.
1. Refer to the documentation for STBY-SPE maintenance.
2. After interchange occurs, run test on new active SPE.
1339 ABORT Could not run the test on the Standby SPEHandshake down.
1. Refer to the documentation for STBY-SPE maintenance.
2. When the standby SPE is restored to service (use status spe to determine
state of standby SPE) retry the command.