DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-777ETR-PT (Enhanced Tone Receiver Port)
9
2000 ABORT Circuit Pack’s response to the test request was not received within the
allowable time period.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2006 ABORT This abort code indicates that the active Tone-Clock circuit pack or a Tone
Detector circuit pack may not be functioning properly.
1. Test the
active
Tone-Clock circuit pack in the port network with the test
tone-clock UUC command.
2. Retry the command at 1-minute intervals a maximum of 5 times.
2100 ABORT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
1-122 FAIL DTMF digits were not detected correctly.
1. Run the short test sequence wth the test port UUCSSpp sh r 1
command.
2. If the problem persists, the system is still operating properly but capacity
is reduced. To restore performance to normal, replace the circuit pack
with the defective ETR-PT.
102 FAIL 2225-Hz Modem Answer Tone was not detected correctly. This impacts
call-classification operation.
1. Run the short test sequence via the test port UUCSSpp sh r 1 command.
2. If the problem persists, the system can still operate properly but capacity
is reduced. In order to restore performance to normal, replace the circuit
pack containing the defective port. Follow the procedures described in
the ‘‘TONE-BD (Tone-Clock Circuit Pack)’’ section for replacing a
tone/clock circuit pack.
130 FAIL Forward or Backward MFC signals were not correctly generated or detected.
This will impact MFC calls.
1. Run the short test sequence via test port UUCSSpp sh r 1.
2. If the problem persists, the system can still operate properly but capacity
will be reduced. In order to restore performance to normal, replace the
TN2182 circuit pack containing the defective ETR-PT. Follow the
procedures described in the ‘‘TONE-BD (Tone-Clock Circuit Pack)’’
section for replacing a tone/clock circuit pack.
PASS Tone Detection Verification is successful. The ETR Port is able to
detect/generate all necessary tones.
Table 9-302. TEST #42 Tone Detection Verification Test — Continued
Error
Code
Tes t
Result Description/ Recommendation
Continued on next page