9-717DUP-CHL (Duplication Interface)
9
Table 9-278. TEST #875 Remote SPE Error Interrupt Test
Error
Code
Te s t
Result Description/ Recommendation
1321 ABORT The faceplate switches on the Duplication Interface circuit packs are not set to
auto.
1. If the switches are locked because you are using a replacement
procedure, continue with this procedure to the step that directs you to
unlock the active SPE by moving both switches to auto. The next step
using the test duplication-interface long clear should not abort with this
error code.
2. If the switches are locked and a replacement procedure is not being used,
start with step 6 of the SPE Duplication Channel Component Replacement
procedure for the standby Duplication Interface Circuit pack at the end of
this DUP-CHL section to avoid an undesired interchange when unlocking
the active SPE.
3. If this same abort is received with both switches in auto, Replace
Duplication Interface components starting with the standby Duplication
Interface circuit pack. Use SPE Duplication Channel Component
Replacement procedures at the end of this DUP-CHL section. In addition
to looking for failures, also check for the absence of this 1321 abort code
when testing after the procedure directs setting the switches to auto after
a component replacement.
1322 ABORT Memory shadowing is off, but not inhibited by the standby SPE.
1. Shadowing may not be turned on yet, so use release spe-standby if the
standby is busied out, wait 5 minutes and run the test again. If the long
duplication-interface demand test was being used, investigate any failure
or abort from test #872 because this test is expected to turn on
shadowing.
2. Rerun the test; if the same 1322 abort occurs again, use the display
alarms command and select Category spe. If any maintenance objects
other than DUPINT or DUP-CHL have MAJOR alarms, fix these problems.
Problems causing MAJOR alarms for MEM-BD, PKT-INT, SYSAM,
H-ADAPTR, and SW-CTL should be repaired first.
3. Rerun the test; if the same 1322 abort occurs again, look for other DUPINT
or DUP-CHL test failures by using the busyout spe-standby if not already
busied out and the test duplication-interface long clear commands. Fix
these problems according to the service documentation for these packs.
4. If this abort continues to occur, the standby SPE may not have initialized
properly. Use the lock-and-power-down procedure described in Chapter 5
to power down and power up the standby SPE, but don’t replace any
circuit packs.
Continued on next page