DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-900H-ADAPTR (MSS Host Adapter)
9
Micro processor testing including exception processing
Private RAM test
EPROM and FLASHPROM checksum test
SPE side Dual Port RAM test
Control and status register test
System memory access test
SCSI bus access test
SCSI memory access test
Sanity timer test
SCSI side Dual Port RAM test
A more complete test of the access to the disk and tape drives over the SCSI bus
is provided by the DISK and TAPE tests.
Table 9-344. TEST #823 Host Adapter Diagnostic Test
Error
Code
Tes t
Result Description/ Recommendation
1316 ABORT Could not allocate the Mass Storage System to run this test. Other application
software may be using it or background maintenance tests may be running.
1. Retry the command at 1-minute intervals for a maximum of 5 retries.
2. If the test continues to abort, verify that the daily translation-save operation
is not in progress (issue the display system-parameters maintenance
command to display the time for scheduled maintenance and the "y/n"
option for saving translation daily).
1335 ABORT Could not run the test on the Standby SPE—Duplication not administered.
1. Refer to “STBY-SPE”.
2. Administer standby present.
1338 ABORT Could not run the test on the Standby SPE—Interchange pending.
1. Refer to “STBY-SPE”.
2. After interchange occurs, run test on new active SPE.
1339 ABORT Could not run the test on the Standby SPE—Handshake down.
1. Refer to “STBY-SPE”.
2. When the standby is restored to service (use status spe to determine state
of standby) retry the command.
Continued on next page