Facility requirements
The facility where the SAN384B is in use must meet the following requirements to
provide for correct operation:
v Adequate supply circuit, line fusing, and wire size, as specified by the electrical
rating on the chassis nameplate
v An air flow of at least 425 cubic meters per hour (250 cubic feet per minute),
available in the immediate vicinity of the SAN384B
v The power specifications listed in Table 25 on page 124
v The environmental specifications listed in Table 24
v If the SAN384B will be installed in an EIA rack, ensure the following:
All equipment installed in the rack has a reliable branch circuit ground
connection, and does not rely on a connection to a branch circuit, such as a
power strip.
The rack is balanced and mechanically secured to provide stability in the
event of an earthquake.
Additional equipment does not exceed the rack's weight limits.
Environmental requirements
Table 24 lists the environmental operating ranges for the SAN384B. The
requirements for non-operating conditions are also provided for acceptable storage
and transportation environments.
CAUTION:
For CA residents only: IBM recommends installing this product in a room size
of 2190 cubic feet (62 cubic meters) or larger at 0.4 ACH ventilation rate to
reduce the concentrations of any chemicals emitted by the product.
Table 24. Environmental requirements
Condition
Acceptable range during
operation
Acceptable range during
nonoperation
Ambient temperature 10° to 40° C outside switch
(50° to 104° F)
-40° to +70° C outside switch
(-40° to 158° F)
Humidity 5% to 85% RH
noncondensing, at 40°
Celsius, with maximum
gradient of 10% per hour
10% to 93% RH
noncondensing, at 70°
Celsius
Altitude Up to 3 km (10,000 ft.) above
sea level
0 to 12 km (40,000 ft.) above
sea level
Shock 20G, 6ms duration, half-sine
wave
33G, 11ms duration, half-sine
wave
Vibration 0.5G p-p, 5-500 Hz at 1.0
octave/minute
2.0G p-p, 5-500 Hz at 1.0
octave/minute
Air flow 425 cu m/hr (250 cu ft/min) None required
Heat dissipation 753 Watts or 2570 BTU/hr
(192 port configuration)
Not applicable.
Note: The 10° to 40° Celsius range applies to the ambient air temperature at the air
intake vents on the nonport side of the SAN384B. The temperature inside
the SAN384B can be up to 75° Celsius during SAN384B operation. If the
Appendix A. Product specifications 123
|
|