Honeywell MRP-2001 Clock Radio User Manual


 
Master Programming Level Programming
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007 71
3.5.7 ANN-BUS
Optional ANN-BUS devices available for the FACP include annunciators, relay modules and
printer connection for acquiring hardcopy printouts of panel data. Pressing 1 while viewing
Programming Screen #3 will cause the control panel to display the following screens.
An ANN-S/PG Printer module, ANN-I/O module, ANN-80 LCD annunciator module, ANN-
RLY relay module and ANN-LED module can be installed in the FACP. These devices
communicate with the FACP over the ANN-BUS terminals on the control panel.
3.5.7.1 ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads
ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN-
BUS Enabled Yes and ANN-BUS Enabled No.
PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST
Programming Screen #3
ANN-BUS
1=BUS ENABLED NO
2=BUS MODULES
3=AUTO CONFIGURE
ANN-BUS Screen #1
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-I/O OPTIONS
3=ANN-80 OPTIONS
ANN-BUS Screen #2
ANN-BUS
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3