Honeywell MRP-2001 Clock Radio User Manual


 
NFPA Standard-Specific Requirements Template 13: Single Hazard - Dual Zone
116 MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
APPENDIX C NFPA Standard-Specific Requirements
This panel has been designed for use in commercial, industrial and institutional applications and
meets the requirements for service under the National Fire Protection Association (NFPA)
Standards outlined in this Appendix. The minimum system components required for compliance
with the appropriate NFPA standard are listed below:
MRP-2001/E Control Panel
Contains the main control board, cabinet (backbox and door), main power supply transformer and
power supply.
Batteries
Refer to "Power Supply Calculations" on page 99, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to one of the control panel's Output Circuits.
Releasing Devices
Connected to one of the control panel's Output Circuits.
The following additional equipment is needed for compliance with the NFPA 72 standards listed
below:
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service
411UD may be installed as illustrated in Figure C.1, “FACP Connection to 411UD,”
on page 117
OR
4XTMF Transmitter Module for connection to the RS82 Remote Station Receiver.
See Figure C.3 on page 120, for installation instructions for this unit
NFPA 72 Auxiliary Fire Alarm System
4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
This unit must be installed as illustrated in the section titled "4XTMF Municipal Box Transmitter
Option Module" on page 28 and as outlined in Figure C.2, “Municipal Box Connected to 4XTMF
Transmitter Module,” on page 119.
NFPA 72 Proprietary Fire Alarm System
FACP Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.4,
“Proprietary Protective Signaling System,” on page 121, for installation instructions for this unit.
The relay contacts of this control panel may be used to trip any dialer that is UL-listed for Central
Station/Remote Station services. The illustrations in this appendix provide examples of possible
system configurations.