Honeywell MRP-2001 Clock Radio User Manual


 
Programming Programming and Passwords
48 MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
3.4 Programming and Passwords
There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in
nonvolatile memory. The factory set passwords can be changed by the user as described in
"Password Change" on page 80. If an invalid password is entered, the blinking cursor will return to
the first password character position. To exit Programming or Read Status mode at any time, press
the ESC (Escape) key repeatedly. Note that as soon as program data is entered, the data is
automatically saved by the panel. If the Reset key is pressed or power is lost before exiting
Programming mode, the data just entered will not be lost.
To access user Programming mode, press the Enter or Mode key. The LCD will display the
following:
To enter the user Programming mode, press 2. The display will read as follows:
Entering the Master
level password (default 00000) will cause the following screen to appear:
If the Maintenance
level password (default 11111) is entered, the following screen will appear:
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.
See Page
1=READ STATUS MODE
2=PROGRAMMING MODE
PROGRAMMING
ENTER PASSWORD
*****
PROGRAMMING
1=FACP CONFIG T5
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST