NFPA Standard-Specific Requirements NFPA 72 Auxiliary Fire Alarm System
120 MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP30 on the MRP-2001/E main circuit board to supervise placement of the
4XTMF module.
2. Refer to "4XTMF Transmitter Module Installation" on page 29 for detailed information.
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver
Model RS82.
+ -
Polarity Shown is
Normal Standby
4XTMF Transmitter Module
Cutting TBL Jumper allows the
reverse polarity circuit to open
with a system trouble condition
if no alarm condition exists.
Power-limited
Figure C.3 Remote Station Connection Using 4XTMF Module
+
-
(Dummy load with a 4.7K
Ω
, ¼ watt
resistor when no connection is made)