Honeywell MRP-2001 Clock Radio User Manual


 
Template 7: Single Hazard - 3 Zone FACP Configuration Templates
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007 109
B.1 Template 7: Single Hazard - 3 Zone
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).
Input Zone Types:
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - no waterflow delay since Waterflow Delay Timer is set to 0
Zone 4 = Manual Release
Zone 5 = Pull Station
Zone 6 = Supervisory
Output Circuit Types:
Output 1 = Alarm NAC
Output 2 = Waterflow NAC - no waterflow delay since Waterflow Delay Timer is set to 0
Output 3 = Release Solenoid 1 (unsupervised for shorts)
Output 4 = Supervisory Bell NAC
Timers
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 0 seconds
AC Loss Delay Timer - set for 2 hours
Operation
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output
#3. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak
Timer 1
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
no FACP initiated delay in activation since the Waterflow Delay Timer is set to 0 seconds
Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #4
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
TEMPLATE 7: SINGLE HAZARD - 3 ZONE
INPUT ZONES
123456
OUTPUT CIRCUITS 2-WIRE SMOKE FIRE WATERFLOW MANUAL
RELEASE
PULL
STATION
SUPV.
#1 ALARM NAC X X X X
#2 WATERFLOW NAC X
#3 RELEASE SOLENOID 1 X X X X
#4 SUPV. BELL NAC X