Chapter 7. PARAMETER SETUP
7-4
7-2 How to Use
PARA
Use
PARA
for calling up individual items in frequently changed parameters.
■ How to register functions to keys
Up to eight individual items in the parameter setup can be assigned to each
PARA
key. The
assignment item must be registered to use this feature.
This feature allows you to call up individual items more easily in the following order:
FUNC
+
PARA
→ selection of setting group → individual item matrix.
● How to register assignment items
To register an assignment item, add the following base corresponding to the setting group
to the item No., and then set the resultant value to setup data C 5 5 to C 6 2 (
PARA
assign-
ment items 1 to 8)).
Base Setting Group
1000 Constant-value operation data
1500 PID parameters
2500 Variable parameters
3500 Event configuration data
4000 Table data
4500 Setup data