Chapter 7. PARAMETER SETUP
7-38
(2) Turn the DCP301 ON again, and set setup data C q 0 setting to 241. For details on
how to change settings, see 7-1 Parameter Setup (page 7-1).
(3) Display the setup data C q 1 setting.
(4) Press
ENT
to display the difference (AB) between the resistances of the Zener bar-
rier connected to leads A and B on the lower display.
(5) Press
ENT
to memorize the difference (AB) between the resistances to the control-
ler.
(6) Press
DISP
to set the DCP301 to the basic display state.
(7) Turn the power OFF, and remove the short across A and B.
The resistance error of the Zener barrier connected to leads A and B cannot be
adjusted unless it is 20 or less.
This adjustment is not required when a Zener barrier and an input other than
an RTD are not used.
Once the Zener barrier has been adjusted, compensation is carried out on the
Zener barrier. When using on an RTD without a Zener barrier, re-adjust without
the Zener barrier.
32
33
34
C
B
A
Zener barrier
Zener barrier
Zener barrier
DCP301
Short-circuit
C q 1 (Input 1 Zener barrier adjustment)
The following adjustment must be made when using a Zener barrier.
(1) Turn the DCP301 OFF. When you have finished mounting and wiring the DCP301,
short-circuit across A and B on the terminals of the RTD.