Sonic Alert DCP301 Clock Radio User Manual


 
Chapter 5. FUNCTIONS
5-17
5-5 Input Processing Functions
Input processing is carried out in the order shown below.
(resistance temperature detector)
(thermocouple)
Input range type
Wiring resistance compensation
Analog input 1
A/D conversion
Cold junction compensation
Upper/lower limit value scaling
Upper/lower limit alarm
Square-root extraction
Temperature unit range
Linearization approximation
Digital filter
Bias
PV1
(DC current and voltage)
Setting: Setup data
C03
Setting: Setup data
C72
Setting: Setup data
C07
(thermocouple and resistance temperature detector)
Setting: Setup data
C02
(DC current and voltage)
Setting: Setup data
C04
to
C06
Setting: Setup data
C08
Table data
T-A.
1
to
T-B.B
Setting: Variable parameter
FL
Setting: Variable parameter
PBi