Chapter 8. PROGRAM SETUP
8-13
■ Inserting and deleting segments
(1) In the setting display state, move to the pattern item of the segment where the seg-
ment is to be inserted or deleted on the programming map.
(2) If you press
FUNC
+
ENT
, the display changes to confirm insertion of the segment,
and “I N S .” is displayed blinking in the upper display.
(3) If you press , the display changes to confirm insertion of the segment, and “I N S .”
is displayed blinking in the upper display.
If you press , the display changes to confirm deletion of the segment, and “D E L .”
is displayed blinking in the upper display.
(4) If you press
ENT
while “I N S .” is displayed on the upper display, the segment is
inserted.
If you press
ENT
while “D E L .” is displayed on the upper display, the segment is
deleted.
(5) The DCP301 returns to the setting display state.
● Display (inserting segment)
● Display (deleting segment)
• When you insert a segment, a new segment is automatically created at the currently
displayed segment No., and all segment Nos. onward are incremented by one. The
setting of the inserted segment is as follows:
SP setting value: Same value as original segment before the new segment was in serted
Time setting value: 0:10
Events, time events and G.Soak are not set, and the PID set No. is set to 0.
• If you try to insert a segment in a program already containing 30 segments, pressing
ENT
will not insert the segment.
• When you delete a segment, the next segment shifts down to the currently displayed
segment No. and subsequent segment Nos. are decremented by one.
When you delete the last segment, the display changes to “- - - -” indicating that noth-
ing is set.
• Segments cannot be inserted or deleted from currently running (RUN, HOLD, FAST,
END) programs.
Program No. Segment No.
Pattern
tendency
EV1 to EV3 and T1 to T5 all out
I N S.
Program No. Segment No.
Pattern
tendency
EV1 to EV3 and T1 to T5 all out
D E L
.