Sonic Alert DCP301 Clock Radio User Manual


 
Chapter 8. PROGRAM SETUP
8-15
8-3 General Reset
A general reset can be executed when the DCP301 is in the READY AUTO mode in the basic display state. If the
DCP301 is not in the basic display state, press
DISP
.
A “general reset” involves the following operations:
Clearing all program setups for program Nos.1 to 19
Returning parameter setups to their factory settings
Changing the mode to the program operation READY AUTO mode
Operation
(1) Set the DCP301 to the READY AUTO mode.
Set variable parameter L O C and P R T C to 0.
(2) If you press
FUNC
+
CLR
+
DISP
in the basic display state, the display changes to con-
firm execution of general reset, and “G . R E S” is displayed on the upper display.
(3) If you press
ENT
, the general reset is executed, and operation starts from startup at
power ON.
If you press
DISP
, general reset is not executed, and the DCP301 returns to the basic
display state.
Display
Program No. Segment No.
Pattern
tendency
Output state of events 1 to 3, time events 1 to 5
G .R E S
In the constant-value operation mode, all of the program No., segment No. and profiles displays
are cleared.
If a RAM backup error occurs when the power is turned ON, the display changes to
confirm general reset without pressing any of the keys on the console, and “G . R E S
is displayed in the upper display.
If you press
ENT
, the general reset is executed. Other keys, however, cannot be oper-
ated.
The following setup data items are not returned to their factory settings.
C 0 2, C 0 3 : Save setting values.
However, note that if a RAM backup error occurs when the power is
turned ON, C 0 2 and C 0 3 settings become 0.
C 0 4, C 0 5: These are set to 0 when the input 1 range type is set to linear.
C 0 6: This is set to 1000 when the input 1 range type is set to linear.