ACC-SVN100A-EN • LonTalk Communication Interface 53
User-defined Types
This section includes:
User-defined network variable types
User-defined configuration property types
These user-defined types have been created by Trane™ for use by Trane controllers. In
many cases, the Trane user-defined types contain standard network variable types
(SNVTs) to make them easy to understand.
User-defined Network Variable Types (UNVTs)
UNVT_purge_information
UNVT_starts_runtime
UNVT_3phase_current
Structure definition
Field in
structure
Byte Bit definition Description
SNVT_state
purge status
Byte 0 (MSB) Bits 0–7 (MSB) Validity of bits 8–15
(1 = Valid)
Bit 8 Refrigeration Circuit On
(1)
Bit 9 Pumping Out (1)
Bit 10 Regenerating (1)
Bits 11–15(LSB) Not Used
SNVT_time_f Byte 1–2 (LSB) Purge 24 Hour
Pumpout Average
Structure definition
Field in structure Definition
SNVT_count_f Compressor Starts
SNVT_time_f Compressor Run Time
Structure definition
Field in structure Definition
SNVT_amp_ac L1 Current (Amps)
SNVT_amp_ac L2 Current (Amps)
SNVT_amp_ac L3 Current (Amps)
SNVT_lev_percent L1 Current (%RLA)
SNVT_lev_percent L2 Current (%RLA)
SNVT_lev_percent L3 Current (%RLA)