![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/b/db/bdb40eff-cf43-49ed-87a9-3eada0e946af/bdb40eff-cf43-49ed-87a9-3eada0e946af-bg2b.png)
ACC-SVN100A-EN • LonTalk Communication Interface 43
Network Variable and Configuration Property Definitions
nvoRfgtDischTmpX
Refrigerant discharge temperature—compressor X,* SNVT_temp_p
nvoRfgtDischTmpA
nvoRfgtDischTmpB
nvoRfgtDischTmpC
nvoRfgtDischTmpD
nvoRfgtDischTmpE
nvoRfgtDischTmpF
This network variable provides the temperature of the refrigerant being discharged from
compressor X (*where X is A, B, C, D, E, or F, depending on the network variable). There
are separate network variables for each compressor.
• Default: 0x7FFF = 327.67°C
• Invalid value: 0x7FFF = 327.67°C
nvoSecCndEntWTmp
Second condenser entering water temperature, SNVT_temp_p
This network variable provides the temperature of the water entering the second
condenser.
• Default: 0x7FFF = 327.67°C
• Invalid value: 0x7FFF = 327.67°C
nvoSecCndLvgWTmp
Second condenser leaving water temperature, SNVT_temp_p
This network variable provides the temperature of the water leaving the second
condenser.
• Default: 0x7FFF = 327.67°C
• Invalid value: 0x7FFF = 327.67°C