34 LonTalk Communication Interface • ACC-SVN100A-EN
Network Variable and Configuration Property Definitions
This network variable provides the pressure of the refrigerant in the condenser on
circuit 3. This refrigerant pressure is sometimes referred to as the condenser discharge
pressure.
• Default: NaN
• Invalid value: NaN
nvoCondRfgtPrsC4
Condenser refrigerant pressure—circuit 4, SNVT_press_f
This network variable provides the pressure of the refrigerant in the condenser on
circuit 4. This refrigerant pressure is sometimes referred to as the condenser discharge
pressure.
• Default: NaN
• Invalid value: NaN
nvoCondRfgtTmpC1
Condenser refrigerant temperature—circuit 1, SNVT_temp_p
This network variable provides the temperature of the refrigerant in the condenser on
circuit 1. This refrigerant temperature is sometimes referred to as the condenser
discharge temperature.
• Default: 0x7FFF = 327.67°C
• Invalid value: 0x7FFF = 327.67°C
nvoCondRfgtTmpC2
Condenser refrigerant temperature—circuit 2, SNVT_temp_p
This network variable provides the temperature of the refrigerant in the condenser on
circuit 2. This refrigerant temperature is sometimes referred to as the condenser
discharge temperature.
• Default: 0x7FFF = 327.67°C
• Invalid value: 0x7FFF = 327.67°C
nvoCondRfgtTmpC3
Condenser refrigerant temperature—circuit 3, SNVT_temp_p
This network variable provides the temperature of the refrigerant in the condenser on
circuit 3. This refrigerant temperature is sometimes referred to as the condenser
discharge temperature.
• Default: 0x7FFF = 327.67°C
• Invalid value: 0x7FFF = 327.67°C
nvoCondRfgtTmpC4
Condenser refrigerant temperature—circuit 4, SNVT_temp_p