28 LonTalk Communication Interface • ACC-SVN100A-EN
Network Variable and Configuration Property Definitions
nviNoiseRdcnReq
Noise reduction Auto/On request, SNVT_switch
This input network variable requests the chiller to enter a mode of operation where the
noise of the unit is reduced. When Noise Reduction is active the chiller reduces speed of
the condenser fans in order to create less noise.
Default: Uses nciNoiseRdcnReq
Invalid value: 0xFF, 0xFF
Valid range (uses 2-state definition of SNVT_switch)
nviRequest
Status request input, SNVT_obj_request
Provides a mechanism for the mode of an object to be requested. Default value will be
adopted at power-up or until an update is received. Does not use the receive heartbeat
function. Responses are received through nvoStatus.
Value
byte
State byte
Resulting
interpretation
Any 0 Auto (0)
01Auto (0)
>0 1 On (1)
Any 0xFF Invalid
Structure definition
Item Type
Enumeration
definition
Default
Invalid
value
Object ID Unsigned 16-bit 0 = node object 65535 65535
1 = chiller object
2 to 65535 are not
valid
Object
request
Unsigned 8-bit enum
object_request_t
See next table:
“Object request”
255 255
Object request
Enumeration definition Description
Controller
interpretation
0 = RQ_NORMAL Enable object and
remove override
Report object status
2 = RQ_UPDATE_STATUS Just report object
status
Report object status
5 = RQ_REPORT_MASK Report status bit mask Report status bit mask
9 = RQ_CLEAR_STATUS Clear object status Report object status
10 = RQ_CLEAR_ALARM Clear object alarm Clear object alarm
16 to 255 = RQ_NUL Value not available Ignore object request
Note: Other enumeration definitions for object_request_t, as defined by LonMark, are not used by
the UC800 controller and have no effect on its operation.