Cooling Capacities
Nominal Cooling (BTU/h) 40,792 48,000 45,500 60,000 55,500
SEER 13 13 13 13 13
Decibels 74 76 76 77 77
Compressor
RLA / LRA 9 / 65.5 12.4 / 88 5.8 / 44 14.7 / 91 7.1/50
Type Recip Scroll Scroll Scroll Scroll
Condenser Fan Motor
Horsepower 1/6 1/4 1/4 1/4 1/4
FLA 1.1 1.5 0.8 1.5 0.8
Refrigeraon System
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) 1⅛" 1⅛" 1⅛" 1⅛" 1⅛"
Refrigerant Charge 83 140 102 167 131
Valve Type Sweat Sweat Sweat Sweat Sweat
Electrical Data
AC Volts/ Hz 208-230/ 60 460/ 60 208-230/ 60 460/ 60
Min. Circuit Ampacity ¹ 12.4 17 8.0 19.9 9.7
Max. Overcurrent Device ² 20 20 15 30 15
Min / Max Volts 197/253 197/253 414/506 197/253 414/506
Electrical Conduit Size ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾"
Ship Weight (lbs) 182 189 207 196 242
¹ Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
² Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
³ Installer will need to supply ¾” to ⅞” adapters for sucon line connecons.
4
Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
Notes
Always check the S&R plate for electrical data on the unit being installed.
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge Procedure.