3.5.1 FACP CONFIG (Application Templates)
For a detailed description of each Template, refer to "FACP Configuration Templates" on page
108. The FACP Configuration option allows the user to program the FACP with one of seven
factory preprogrammed templates or one custom template which can be programmed by the user.
The templates have been provided to allow the user to quickly program the panel with typical job-
site configurations. The user may choose to select one of the templates or bypass this option,
proceeding to the next sections which detail customized programming of the FACP.
A factory template may be chosen and later changed to better fit a site requirement. The changed
template can be saved as the one custom template.
Pressing 1, while viewing Programming Screen #1, will select the FACP Config option and display
the following screen:
Pressing the down arrow key will display screens for additional Templates and the Custom
Template. During initialization of the panel following power-up or reset, the selected Template will
be displayed by the LCD.
Note: Only Templates 7 through 13 are available for the MRP-2001/E Pre-Action/Deluge Control
Panel.
To select a pre-programmed templates, press the number key corresponding to the desired template.
Note that the factory templates may pre-set most programmable features of the FACP.
3.5.2 Input Zones
The Input Zones option allows the user to initially program or change the programming for the six
input zones (circuits). Pressing 2, while viewing Programming Screen #1, will select the Input
Zones option and display a screen similar to the following:
Pressing the down arrow key will display additional screens for Input Zones 4 through 6. To
program a specific zone, press the number key corresponding to the desired zone while viewing one
of the Input Zone screens.
To program Input Zone 1, press the 1 key while viewing Input Zone Screen #1. The following
screens will be displayed:
PROGRAMMING
1=FACP CONFIG USER
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
FACP CONFIG
1=N/A
2=N/A
3=N/A
FACP Config Screen #1
INPUT ZONES
1=ZONE 1
2=ZONE 2
3=ZONE 3
Input Zone Screen #1
INPUT ZONE 1
Normal PULL STATION
PRESS TO EDIT
Edit Input Zone Screen #1