Honeywell MRP-2001E Clock Radio User Manual


 
Template 11: Single Hazard - 3 Zones and Low Pressure FACP Configuration Templates
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007 113
B.5 Template 11: Single Hazard - 3 Zones and Low Pressure
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Input Zone Types:
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Zone 4 = Manual Release
Zone 5 = Pull Station
Zone 6 = Low Pressure
Output Circuit Types:
Output 1 = Alarm NAC
Output 2 = Waterflow NAC - activation delayed for 10 secs. (Waterflow Delay set to10 secs.)
Output 3 = Supervisory Bell NAC
Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output
#4. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak
Timer 1
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
TEMPLATE 11: SINGLE HAZARD - 3 ZONES AND LOW PRESSURE
INPUT ZONES
123456
OUTPUT CIRCUITS 2-WIRE SMOKE FIRE WATERFLOW MANUAL
RELEASE
PULL
STATION
LOW
PRESS.
#1 ALARM NAC X X X X
#2 WATERFLOW NAC X
#3 SUPV. BELL NAC X
#4 RELEASE SOLENOID 1 X X X X