Initial Power-up Programming
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007 47
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized
person. After pressing 2, a screen will prompt for a password. After entering the correct password,
the user may select from a list of programming options.
Exit Programming and Read Status Mode
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the
display reads System All Normal. Note that the data which is entered during Programming mode
is automatically saved by the panel as soon as the data is entered. If the Reset key is pressed or
power is lost before exiting Programming mode, all data just entered will not
be lost.
User Programming Levels
There are two user programming levels:
User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.
3.2 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of devices to the FACP, apply power to the control panel. If wiring has
not been completed and/or End-of-Line resistors are not installed at the panel, a trouble condition
will be indicated at the panel and a trouble message will be displayed on the LCD. Following is an
example of a possible trouble message that may be displayed.
3.3 Programming Screens Description
Two options are available when the Enter key is pressed: Read Status and Programming Mode.
The Read Status and Programming options have multiple functions or features which may be
chosen. To view all of the choices, it is necessary that the programmer scroll through a number of
additional subscreens. These selections are displayed on multiple screens to make them more
readable for the programmer. Refer to "Master Programming Level" on page 49, for additional
information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the
programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed
in the upper right corner of the screen being viewed. The programmer can then press the keypad
Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the
programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is followed to view all option choices.
OPEN PULL STATION
ZONE 1 OPEN FAULT
09:03A 012106
See Page