FACP Configuration Templates Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active
114 MRP-2001 & MRP-2001E PN 53040:A 4/16/2007
B.6 Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Cx = cross-zone where x is the number of the Release Solenoid. All inputs with the same Release Solenoid
number must be active at the same time to turn on the corresponding solenoid output circuit
Input Zone Types:
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Zone 4 = Manual Release
Zone 5 = Pull Station
Zone 6 = Low Pressure
Output Circuit Types:
Output 1 = Alarm NAC
Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
Output 3 = Supervisory Bell NAC
Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
Activation of both Input Zone 1 (2-Wire Smoke) and Zone 2 (Fire) at the same time, or Zone
4 (Manual Release) or Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #4.
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer
1. Activation of any one of these zones will operate Alarm NAC Output #1
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
TEMPLATE 12: SINGLE HAZARD - 2 ZONES CROSS-ZONES WITH ALL ACTIVE
INPUT ZONES
123456
OUTPUT CIRCUITS 2-WIRE SMOKE FIRE WATERFLOW MANUAL
RELEASE
PULL
STATION
LOW
PRESS.
#1 ALARM NAC X X X X
#2 WATERFLOW NAC X
#3 SUPV. BELL NAC X
#4 RELEASE SOLENOID 1 C1 C1 X X