Template 9: Dual Hazard - Combined Release FACP Configuration Templates
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007 111
B.3 Template 9: Dual Hazard - Combined Release
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Input Zone Types:
• Zone 1 = 2-wire smoke
• Zone 2 = Fire
• Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
• Zone 4 = Manual Release
• Zone 5 = Pull Station
• Zone 6 = Supervisory
Output Circuit Types:
• Output 1 = Alarm NAC
• Output 2 = Supervisory Bell NAC
• Output 3 = Release Solenoid 1 (unsupervised for shorts)
• Output 4 = Release Solenoid 2 (unsupervised for shorts)
Timers
• Soak Timer 1 - set for 10 minutes
• Soak Timer 2 - set for 10 minutes
• Waterflow Delay Timer - set for 10 seconds
• AC Loss Delay Timer - set for 2 hours
Operation
• Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1, Release Solenoid 1 Output #3
and Release Solenoid 2 Output #4. Release Solenoid 1 will turn off water release following
time-out of the 10 minute Soak Timer 1 and Release Solenoid 2 will turn off water release
following time-out of the 10 minute Soak Timer 2
• Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
• Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #2
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
• Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
• Trouble Relay - any system trouble will activate the Trouble Relay
• Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
TEMPLATE 9: DUAL HAZARD - COMBINED RELEASE
INPUT ZONES
123456
OUTPUT CIRCUITS 2-WIRE SMOKE FIRE WATERFLOW MANUAL
RELEASE
PULL
STATION
SUPV.
#1 ALARM NAC X X X X X
#2 SUPV BELL NAC X
#3 RELEASE SOLENOID 1 X X X X
#4 RELEASE SOLENOID 2 X X X X