A SERVICE OF

logo

XP128 Hardware 45
Table 8 (page 45) lists the basic AC power requirements for three-phase
operation of the XP128 DKC.
Table 8. 30-Amp, 50 or 60 Hz, Three-Phase DKU Operation
Parameter
Nominal Rated Voltage (Vac)
200 208
*
220 230 240 380 400 415
Rated line current per
power cord (Arms)
11.1 10.7 10.0 9.6 9.1 6.0 5.5 5.3
Number of power
cords
2 2 2 2 2 2 2 2
Number of circuit
breakers
2 2 2 2 2 2 2 2
Recommended circuit
breakers
30 A 30 A 30 A 30 A 30 A 30 A 30 A 30 A
* 60 Hz only.