Cisco TelePresence System 3200
OL-14521-01
Chapter 9 Routing Power and Signal Cables
Parts List
Warning
Output receptacles cannot exceed 15A for any one receptacle.
Caution Correct routing of the various power cords to the appropriate PDU is critical for the safety and success
of the Cisco TelePresence System 3200 assembly. Each PDU is routed to a different 20A circuit to
prevent circuit overload when all the electrical components are properly installed. PDUs should be
plugged into their correct wall receptacles as required in the following table.
Note For cable routing for the second row table, see Chapter 7, “Building the Second Row Table Assembly.”
Left PDU 1
(Located on Left Accessory Cabinet.)
Left 20A AC wall outlet
Left PDU 2
(Located on Left Accessory Cabinet.)
Center left 20A AC wall outlet
Right PDU
(Located on Right Accessory Cabinet.)
Center right 20A AC wall outlet
First Row Table PDU
(Located above the projector under the Center
table segment.)
Right 20A AC wall outlet
Second Row Table left-center PDU 20A AC wall outlet
Second Row Table right-center PDU 20A AC wall outlet