Appendix A - Site Planning Data 63
Table 4 Site Planning Data, 480 Volt Input
UPS Rating AC
Output
Voltage
Options Rectifier AC
Input Current
Inverter or
Bypass
Output
Current
Required
Battery
Discon-
nect
Maximum
Battery
Current at
End of
Maximum
Heat Dissi-
pation
(BTU/Hr)
Dimensions
Inches
Approx.
Weight
Floor
Loading
(Lb/Sq Ft)
(concen-
kVA kW
Input
Filter
Input
Xfmr
Nom Max Nom Max
Rating
(Amperes
)
Dis-
charge
(Amperes)
Full Load
(WxDxH) (unpacked
)
trated
loading)
500 400 480 NO NO 602 753 601 752 1,000 1,079 87,150 72x39x79 5,775 296
500 400 480 YES NO 558 698 601 752 1,000 1,079 91,800 72x39x79 5,975 306
500 400 480 NO YES 612 765 601 752 1,000 1,079 110,700 96x39x79 8,775 338
500 400 480 YES YES 565 707 601 752 1,000 1,079 115,500 96x39x79 8,975 345
500 450 480 NO NO 677 847 601 752 1,200 1,214 98,050 72x39x79 5,795 297
500 450 480 YES NO 628 785 601 752 1,200 1,214 103,250 72x39x79 5,995 307
500 450 480 NO YES 688 861 601 752 1,200 1,214 124,550 96x39x79 9,095 350
500 450 480 YES YES 638 798 601 752 1,200 1,214 129,931 96x39x79 9,295 358
625 500 480 NO NO 749 936 752 936 1,400 1,349 99,300 108x39x79 7,500 256
625 500 480 YES NO 694 867 752 936 1,400 1,349 105,050 108x39x79 7,720 264
625 500 480 NO YES 757 946 752 936 1,400 1,349 118,650 120x39x79 10,580 326
625 500 480 YES YES 701 877 752 936 1,400 1,349 124,509 120x39x79 10,800 332
750 600 480 NO NO 898 1123 902 1128 1,600 1,619 119,200 108x39x79 8,100 277
750 600 480 YES NO 833 1041 902 1128 1,600 1,619 126,100 108x39x79 8,320 284
750 600 480 NO YES 908 1135 902 1128 1,600 1,619 142,350 120x39x79 11,580 356
750 600 480 YES YES 842 1052 902 1128 1,600 1,619 149,410 120x39x79 11,800 363
750 675 480 NO YES 1022 1277 902 1128 1,600 1,822 160,150 120x39x79 11,880 366
750 675 480 YES YES 947 1184 902 1128 1,600 1,822 168,100 120x39x79 12,100 372
13 1,4,5,7,8,
9,11,12
2,3,5,7,8,
9,11,12
66,8,9,
11,12